E84AYCEC communication manual (Ethernet POWERLINK)

Installation

Electrical installation

5.2.2

Network topology

[5-4]

Network topology for Ethernet POWERLINK

Inside the segment only Ethernet hubs may be used as infrastructure elements. The hubs

must meet the requirements on class II repeaters acc. to IEEE 802.3u.
For this purpose Lenze offers the dual hub integrated into the communication module and

the separate eight-fold hub, type E94AZCEH.
Class I hubs and switches are not permissible since they have considerably longer delay

times for the frame forwarding and a bigger jitter. Both sizes reduce the real-time

capability and dynamics.
The cable length between both nodes is limited to 100 m.
The topology rules (IEEE 802.3u) required for controlling the collisions may be violated in

the EPL network segment since according to the EPL access order frame collisions are

prevented. This enables a structure of lines and any hybrid forms between star and line

topology.

Note!

The use of class I hubs and switches inside the EPL network segment is not

permitted.