EDS84AYCEC EN 3.0 - 09/2012

L

31

E84AYCEC communication manual (Ethernet POWERLINK)

Installation

Electrical installation

5.2.5

Ethernet POWERLINK connection

Ethernet POWERLINK is connected via the RJ45 sockets X251 (P1) and X252 (P2).

[5-6]

Ethernet POWERLINK connections X251 (P1) and X252 (P2)

 If possible, do not wire more than 10 nodes in a row in a network line.
 In case of more than 10 nodes you should deactivate the automatic calculation of the

hub level in the »Engineer« and enter it manually to increase the performance.

 With a cycle time of 1 ms, 25 nodes can be operated.

– The number of nodes can be increased if the EPL cycle time is increased as well.

 You can use a standard Ethernet patch cable to connect the communication module to

the Ethernet POWERLINK fieldbus (see

Ethernet cable specification

( 33)

).

 The installation and removal of the Ethernet cables is optimised for use of connectors

according to the "Automation Initiative of German Domestic Automobile

Manufacturers" (AIDA).

E84YCEC001E

Note!

To prevent the RJ45 socket from being damaged, hold the Ethernet cable

connector straight (at a right angle) when inserting it into or removing it from

the socket.