E84AYCEC communication manual (Ethernet POWERLINK)

Installation

Electrical installation

28

L

EDS84AYCEC EN 3.0 - 09/2012

Recommended topology
For an easy configuration and due to many possible topology variants we recommend to

create networks according to the following rules:

1. Create CN groups with up to 10 nodes.
2. Connect CN groups in star shape to the managing node.
3. Connect CN groups to the managing node via one external hub each.

– For more than 2 CN groups, use an external 8-port hub (e.g. Lenze hub E94AZCEH).
– For max. 7 CN groups one hub is sufficient.
– For more than 7 CN groups, use further hubs.
– The groups can be distributed on the hubs just as you like.
– Observe the restrictions of the used managing node.

[5-5]

Star topology for 1 to 2 CN groups

Note!

E94AYCEP communication module als Managing Node
With maximally 2 CN groups and the use of an E94AYCEP communication

module as Managing Node, connect the CN group(s) directly to the Ethernet

POWERLINK terminals X211 and X212 of the E94AYCEP communication module.

E94YCEP033

1. CN group

2. CN group

Managing

Node

Hub