C13861 | 0x1f8c nmt communication status, C13864 | 0x1f93.1 node id, C13865 | 0x1f93.2 node id by hw – Lenze E84AYCEC User Manual

Page 76: C13861, And the red, E84aycec communication manual (ethernet powerlink)

Advertising
background image

E84AYCEC communication manual (Ethernet POWERLINK)

Parameter reference

Parameters of the communication module

76

L

EDS84AYCEC EN 3.0 - 09/2012

C13861

C13864

C13865

Parameter | Name:

C13861 | 0x1F8C NMT Communication Status

Data type: UNSIGNED_8

Index: 10714

d

= 29DA

h

The code displays the current NMT state (according to the Ethernet POWERLINK specification) of the EPL node.
Selection list

(read only)

Info

0 Off

NMT_GS_OFF

25 Initialising

NMT_GS_INITIALISING

41 ResetAppl

NMT_GS_RESET_APPLICATION

57 ResetComm

NMT_GS_RESET_CONFIGURATION

121 ResetConfig

NMT_GS_RESET_CONFIGURATION

28 NotActive

NMT_CS_NOT_ACTIVE

29 PreOp1

NMT_CS_PRE_OPERATIONAL_2

93 PreOp2

NMT_CS_PRE_OPERATIONAL_2

109 ReadyToOp

NMT_CS_READY_TO_OPERATE

253 Operational

NMT_CS_OPERATIONAL

77 Stopped

NMT_CS_STOPPED

30 BasicEthernet

NMT_CS_BASIC_ETHERNET

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13864 | 0x1F93.1 Node ID

Data type: UNSIGNED_8

Index: 10711

d

= 29D7

h

The code displays the currently valid EPL node address (Node ID).

• The node ID must be unequivocal in the EPL network segment.

• See also

C13899

.

Display range

(min. value | unit | max. value)

1

239

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13865 | 0x1F93.2 Node ID by HW

Data type: UNSIGNED_8

Index: 10710

d

= 29D6

h

The code indicates whether the EPL node address (node ID) has been set via rotary encoder switches at the

communication module or via the software.

• 0 (FALSE): Node ID has been set via software (

C13899

).

• 1 (TRUE): node ID has been set via rotary encoder switches at the communication module.

Node address setting ( 38)

Display range

(min. value | unit | max. value)

0

1

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT