E84AYCEC communication manual (Ethernet POWERLINK)

Parameter reference

Parameters of the communication module

78

L

EDS84AYCEC EN 3.0 - 09/2012

C13887

C13898

C13899

C13900

Parameter | Name:

C13887 | Suppress emergency message upon

Data type: BITFIELD_8

Index: 10688

d

= 29C0

h

This code serves to suppress sending alarm messages to the managing node. You can explicitly suppress a certain

type of error. Furthermore, all errors are entered into the logbook.

• A change can only be effective immediately if no error number with the error type selected here is active in

C00165.

Value is bit-coded:

Bit 0 Fault
Bit 1 Fault
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13898 | 0x1F9A Host Name

Data type: VISIBLE_STRING

Index: 10677

d

= 29B5

h

The code defines a DNS-compatible device name. The length is limited to 20 characters. The device name must be

non-ambiguous within the network domain.

Naming convention:

The device name ...

• starts with a letter;

• ends with a letter or a digit.

The device name consists of ...

• letters (A ... Z, a ... z);

• digits (0 ... 9);

• hyphen (-).

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13899 | 0x1F93.3 Node ID by SW

Data type: UNSIGNED_8

Index: 10676

d

= 29B4

h

This code serves to set the node ID by means of the software.

The value "0" is not a valid node ID. It serves to activate the setting via the rotary coding switches.

Node address setting ( 38)

Setting range

(min. value | unit | max. value)

Lenze setting

0

239 0

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT

Parameter | Name:

C13900 | Firmware Type

Data type: VISIBLE_STRING

Index: 10675

d

= 29B3

h

Display of the Lenze firmware type of the communication module (product designation).

Read access  Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT