E84AYCEC communication manual (Ethernet POWERLINK)

Error messages

Possible causes and remedies

EPL: Invalid module configuration [0x01bc6430]

EPL: State OPERATIONAL lost [0x01bc8131]

EPL: Invalid address selected [0x01bc8261]

EPL: Synchronisation lost from MN [0x01bc8265]

EPL: Telegram error detected (CRC) [0x01bc8266]

Response (Lenze setting in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Module configuration is faulty.

Check the module configuration and correct it.

Response (Lenze setting in bold)

Setting:

C13880/1

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Data exchange via Ethernet POWERLINK has been

terminated.

• See also chapter "

Interruption of Ethernet

POWERLINK communication

"

( 52)

.

• Check the network cable (plug) and replace it if

necessary.

• Connect the network cable to the Ethernet

POWERLINK terminals X251 or X252 and continue to

check the status of the managing node.

Response (Lenze setting in bold)

Setting: not possible

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

An invalid IP address has been assigned by the managing

node via Ethernet POWERLINK or set as node ID.

• Ensure that a valid IP address is assigned by the

managing node via Ethernet POWERLINK.

• Set valid node ID.

Node address setting ( 38)

Response (Lenze setting in bold)

Setting:

C13880/2

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

In the controlled node, the synchronisation cycle of the

managing node has failed. The controlled node changes

automatically to the NMT_CS_PREOPERATIONAL_1

state and waits for a new run-up by the managing node.

• Check network cable and components (failure of

managing node, router).

• Restart managing node if required.

Response (Lenze setting in bold)

Setting:

C13880/3

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Faulty Ethernet frames (CRC error) have been detected.

Possible causes:

• A device in the network is not EPL-compliant.

• EMC interference is too strong.

• Check if a non-EPL-compliant device is in the network

(e.g. diagnostics PC).

• Reduce EMC interference on the network or use an

additional shield connection.