Node address setting

38

L

EDS84AYCEC EN 3.0 - 09/2012

6.2

Node address setting

The node address is set via the two front panel rotary coding switches "Node ID".

[6-1]

Rotary coding switches "Node ID"

 The labelling of the rotary coding switches corresponds to the values for determining

the node address.

 Valid addresses for the communication module in the EPL network:

– 1 … 100: Controlled node with Lenze module E94AYCEP as managing node
– 1 … 239: Controlled node with managing node of another manufacturer

 The corresponding Ethernet IP address of the communication module results from the

address setting of the rotary coding switches:
– IP address: 192.168.100.[EPL address]

Note!

• Each network node address must only be used once.
• The node address setting in the configuration software (e.g. »Engineer«) and

the rotary encoder switches must be identical for each node.

• Adjustable address range: 1 ... 239
• Switch the voltage supply of the communication module off and on again to

activate changed settings.