E84AYCEC communication manual (Ethernet POWERLINK)

Diagnostics

Troubleshooting with module signalling

[9-3]

Diagnostics - Ethernet POWERLINK operation

E94YCEP053

3. Diagnostics - EPL operation

Make further error
search with the
Engineer.

Go back to point 3.

Standard device: Make a
fault reset.
Then wait 30 s.

EPL master:

ME on?

Make a fault reset

at the standard

Device.

End

Wait 30 s.

EPL master: BS

on / blinking?

yes

no

yes

on

blinking / off

no

End

on

Make further error
search with the
Engineer.

Wait 30 s.

EPL master: BS

on / blinking?

EPL master:

ME on?

BE on?

blinking / off

Note!

The LEDs ME (Module Error), BE (Bus Error) and BS (Bus State) refer to the Lenze

communication module E94AYCEP as managing node.
These status displays apply analogously to the managing nodes of other

manufacturers.