Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17

105

14

Parameter reference

14.3

Parameters of the communication module for slot MXI2

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C14863

C14864

C14865

C14866

Parameter | Name:

C14863 | Baud rate

Data type: UNSIGNED_8

Index: 9712

d

= 25F0

h

Display of the baud rate
Selection list

(read only)

0 12.00 Mbps
1 6.00 Mbps
2 3.00 Mbps
3 1.50 Mbps
4 500.00 kbps
5 187.50 kbps
6 93.75 kbps
7 45.45 kbps
8 19.20 kbps
9 9.60 kbps

15 No baud rate detected

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C14864 | Active station address

Data type: UNSIGNED_8

Index: 9711

d

= 25EF

h

Display of the active station address

If all DIP switches 1 ... 64 are in the "OFF" position (Lenze setting), the station address set in

C14899

becomes active

and is displayed here after switching on.



Setting the station address ( 31)

Display area

(min. value | unit | max. value)

0

255

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C14865 | Display: Most recent PRM data

Data type: OCTET_STRING

Index: 9710

d

= 25EE

h

Display of the last parameter data sent by the PROFIBUS master with the "Set-Prm" telegram (ASCII string with 24

characters)

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C14866 | Display: Most recent CFG data

Data type: OCTET_STRING

Index: 9709

d

= 25ED

h

Display of the last configuration data sent by the PROFIBUS master with the "Chk-Cfg" telegram (ASCII string with

22 characters)

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT