5.2
Electrical installation
24
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
If the communication module is supplied externally, the bus terminator can be supplied
independently of the standard device supply.
Activating the bus terminating resistor
Number of stations
[5-5]
Number of stations
Tip!
Repeaters do not have a station address. When calculating the maximum number of
stations, they reduce the number of stations by 1 on each side of the segment.
Repeaters can be used to build up line and tree topologies. The maximum total bus system
expansion depends on ...
• the baud rate used;
• the number of repeaters used.
Note!
The bus terminator must always be supplied. Otherwise, the bus can get unstable.
2133PFB004