3 advanced diagnostic message, 12 diagnostics – Lenze E94AYCPM User Manual

Page 85

Advertising
background image

Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17

85

12

Diagnostics

12.3

Advanced diagnostic message

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.3

Advanced diagnostic message

Errors in the standard device and its plugged-in modules are transmitted to the PROFIBUS master in

the form of advanced diagnostic messages.

Structure of the diagnostic message

Byte

Description

1 Bit 0: Station does not exist (set by the master).

Bit 1: Slave is not ready for data exchange.

Bit 2: Configuration data do not correspond.

Bit 3: Slave has extended diagnostic data.

Bit 4: Requested function is not supported by the slave.

Bit 5: Slave response is invalid (set by the master)

Bit 6: Incorrect parameter setting

Bit 7: Slave has been parameterised by another master (set by the master).

2 Bit 0: Slave must be parameterised again.

Bit 1: Static diagnostics

Bit 2: Permanently set to "1".

Bit 3: Watchdog active

Bit 4: Freeze command received.

Bit 5: Sync command received.

Bit 6: Reserved

Bit 7: Slave is deactivated (set by the master).

3 Bit 7: Diagnostics overflow - amount of diagnostic information present in the slave is too large to fit

into one telegram.

4 Bits 0 ... 7: Master address after parameter setting ("0xFF" without parameterisation)
5 Bits 0 ... 7: ID number (high byte)
6 Bits 0 ... 7: ID number (low byte)
7 Header

• The header contains the block length of the advanced diagnostics including the header byte.

• In this case, the value of the entry is "0x0A" (bytes 7 ... 16 = 10 bytes).

8 Status_Type

The value of this entry is fixed. For the following bit assignment it is "0x81":

• Bit 7 = 1: "status"

• Bit 0 = 1: "status message"

• Value of all other bits = 0

9 Slot_Number

The value of the slot number is "0x00".

10 Specifier

• A detected error is entered in the specifier with the identification "0x0" (status coming).

• An eliminated error is entered in the specifier with the identification "0x02" (status going).

• If no errors are indicated, the entry in the specifier has the value "0x00" (no further

differentiation).

11 PROFIsafe, error number of the safety module SM301 (E94AYAE)

• If an error occurs in the safety module, byte 11 (low byte) and byte 12 (high byte) contain the

corresponding error number.

• See also documentation for the safety module.

12

13 ... 16 Error code of the Servo Drive 9400

• Code C00168 can be used to read out the contents of the fault memory.

• Detailed information on the error codes of the Servo Drive 9400 can be found in the

documentation of the controller.

Advertising