Possible DIP switch settings

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.3

Possible DIP switch settings

[6-1]

DIP switch

6.3.1

Setting the station address

The station addresses must differ from each other if several networked PROFIBUS stations are used.
The station address can be set via the DIP switches 1 ... 64 or via the »Engineer« (code

C13899

/

C14899

).

The housing labelling indicates the valencies of the individual DIP switches for setting the station

address.

• Valid address range: 1 … 126 (max. 126 slave stations)

C13920

/

C14920

: Display of the current address setting of the switches

C13864

/

C14864

: Display of the station address active on the PROFIBUS

E94YCPM001D

The front-panel DIP switches can be used to set:

• The station address (switches 1 ... 64)
• Compatibility with the communication module EMF2133IB

(switch 2133)

Lenze setting: all switches in OFF position

Setting the station address via ...
DIP switch

C13899 / 14899

Condition

At least one switch 1 … 64 = ON

• Switches 1 ... 64 = OFF

• Switch 1 ... 64 = ON

(invalid value "127")

DIP switch

64

32

16

8

4

2

1

Switch position

OFF

OFF

ON

OFF

ON

ON

ON

Value

0

0

16

0

4

2

1

Station address

= sum of the valencies = 16 + 4 + 2 + 1 = 23



DIP switch positions for setting the station address ( 116)

Note!

Switch off the voltage supply of the communication module and then on again in order

to activate changed settings.