C13867 | display: most recent diagnostic data, C13868 | display: dp state, C13880 | reaction on communication fault – Lenze E94AYCPM User Manual

Page 97: Terised under, C13880/1, C13868, C13880/2, 14 parameter reference

Advertising
background image

Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17

97

14

Parameter reference

14.2

Parameters of the communication module for slot MXI1

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C13867

C13868

C13880

Parameter | Name:

C13867 | Display: Most recent diagnostic data

Data type: OCTET_STRING

Index: 10708

d

= 29D4

h

Display of the last diagnostic data sent to the PROFIBUS master (ASCII string with 16 characters)



Advanced diagnostic message ( 85)

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13868 | Display: DP state

Data type: UNSIGNED_8

Index: 10707

d

= 29D3

h

Available from software version 01.21!

Display of the DP states (Decentralized Peripherals)



Short-time interruption of PROFIBUS communication ( 79)

, see fig.

[11-1]

Selection list

(read only)

0 Waiting for parameterisation
1 Waiting for configuration
2 Data exchange
3 n/a

;

Read access … Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13880 | Reaction on communication fault

Data type: UNSIGNED_8

Index: 10695

d

= 29C7

h

Monitoring response to a communication fault on the PROFIBUS

A change in the monitoring response is effective immediately.



Permanent interruption of PROFIBUS communication ( 78)

Selection list

0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
6 Information

Subcodes

Lenze setting

Info

C13880/1

0: No response

The response set here for the "Watchdog/Data

Exchange" monitoring function is executed if the bus

station ...

• does not receive a message from the master within

the watchdog monitoring time (displayed in

C13882/

1

) if there is an active connection.

• detects that it is no longer in the "Data_Exchange"

status. Please see also the notes given under

C13881

.

C13880/2

0: No response

The response set here for the "DPV1 MSAC2" monitoring

is executed if the bus station does not receive a "DPV1

MSAC2" message from the master within the monitoring

time (displayed in

C13882/2

) if there is an active

connection) and the MSAC2 connection is stopped by the

slave.

Note: We recommend only setting "information" as

response so that no drive-relevant response is executed.

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Advertising