Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17

89

13

Error messages

13.2

Possible causes and remedies

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Profibus: Internal error [0x00c86011]

Profibus: Internal error [0x00c86100]

Profibus: Internal error [0x00c86101]

Profibus: Internal mapping error [0x00c86110]

Profibus: Invalid parameter set [0x00c8641f]

Profibus: Error: Lenze setting loaded [0x00c86420]

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Module defective.

If this occurs repeatedly, contact the Lenze service.

Response (Lenze setting printed in bold)

Setting: not possible

:

None … System fault … Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Internal error.

If this occurs repeatedly, contact the Lenze service.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

The communication module carries out an automatic

software reset and reinitialises itself.

If this occurs repeatedly, contact the Lenze service.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault … Fault … Trouble … Quick stop by trouble : Warning locked … Warning … Information

Cause

Remedy

The selected PDO mapping is invalid:

• An object not supporting the required properties has

been specified.

• More than 64 bytes of data have been mapped.

Repeat the PDO mapping.

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

No active parameter set could be loaded.

Repeat the download of the application

(including module)

Response (Lenze setting printed in bold)

Setting: not possible

…

None … System fault : Fault … Trouble … Quick stop by trouble … Warning locked … Warning … Information

Cause

Remedy

Access to parameter set was not successful.

Repeat the download of the application

(including module).