PROFIsafe

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10

PROFIsafe

PROFIBUS enables the transfer of safe information via the PROFIsafe protocol in accordance with

the "PROFIsafe - Profile for Safety Technology" specification, version 2.0.

• The PROFIsafe data are sent in the first slot of a PROFIBUS data telegram.
• One bit of the PROFIsafe data is always used to control specific safety functions.
• The structure of the PROFIsafe data is described in the PROFIsafe profile.
• The length of the PROFIsafe data (also called PROFIsafe message) always is 8 bytes.

Note!

A safety bus system (PROFIsafe) can only be operated via the upper module slot MXI1 of

the Servo Drive 9400.

Documentation for the safety module SM301 (E94AYAE)
Here you can find detailed information on the PROFIsafe connection.