11 monitoring – Lenze E94AYCPM User Manual

Page 79

Advertising
background image

Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17

79

11

Monitoring

11.2

Short-time interruption of PROFIBUS communication

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11.2

Short-time interruption of PROFIBUS communication

From software version 01.21, the current DP states are displayed in C13868 / C14868.

[11-1] DP states (Decentralized Peripherals) for short-time interruption of communication

The master detects the communication fault and transfers the slave to the "WAIT_PRM" state of the

DP state machine after only a few microseconds (see Fig.

[11-1]

).

Only after the state chain of the DP state machine ending in the "Data_Exchange" state

(DATA_EXCH) has been passed through, the watchdog monitoring time calculated for the slave (in

milliseconds) continues to run.

Additional monitoring for the data exchange
An additional monitoring function for data exchange is available under

C13881

/

C14881

. This

monitoring function already becomes active when the "Data_Exchange" state is exited and the

parameterised time (0 ... 65535 ms) has expired. The active monitoring function triggers the

response parameterised under

C13880/1

/

C14880/1

.

2133PFB006

POWER ON

WAIT_PRM

WAIT_CFG

DATA_EXCH

Slave_Diag
Get_Cfg

Set_Slave_Add

Slave_Diag

Chk_Cfg, not o.k.
Set_Prm, not o.k.

Chk_Cfg, o.k.

Slave_Diag
Set_Prm
Get_Cfg

Note!

The watchdog monitoring time does not continue to run when the slave does not reach

the "Data_Exchange" state due to repeated communication errors (e.g. caused by loose

contact).

Note!

Observe the following condition for the time setting:
Monitoring time for data exchange (

C13881

/

C14881

)

watchdog monitoring time of

PROFIBUS (

C13882/1

/

C14882/1

).