11 monitoring, 1 permanent interruption of profibus communication, Monitoring – Lenze E94AYCPM User Manual

Page 78

Advertising
background image

11

Monitoring

11.1

Permanent interruption of PROFIBUS communication

78

Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11

Monitoring

11.1

Permanent interruption of PROFIBUS communication

If PROFIBUS communication is interrupted permanently, e.g. by cable breakage or failure of the

PROFIBUS master, no process data are transmitted to the slave being in the "Data Exchange" state.
After the watchdog monitoring time determined by the PROFIBUS master has expired, the response

parameterised under

C13880/1

/

C14880/1

is executed in the controller (slave).

The process data handling depends on the setting in

C13885

/

C14885

. (The last data sent by the

master can either be used or set to zero.)

Preconditions for a controller (slave) response

• A monitoring time of 1 ... 65534 ms is set for the "Data_Exchange" state (

C13881

/

C14881

).

A value of "65535 ms" (Lenze setting) deactivates the monitoring.

• A response is set for the slave in

C13880/1

/

C14880/1

(Lenze setting: "No response").

• The slave is in the "Data_Exchange" state.
• The watchdog monitoring time is configured correctly in the master.

If one of these preconditions is not met, the response to the absence of cyclic process data telegrams

from the master is not executed.



Settings and displays in the »Engineer«

( 80)

Advertising