Technical data

Protective insulation

4

l

16

EDS82ZAFVCxxx EN 4.0

4.3

Protective insulation

{

Danger!

Dangerous electrical voltage
If Lenze controllers are used on a phase earthed mains with a rated mains
voltage

³ 400 V, protection against accidental contact is not ensured without

implementing external measures.
Possible consequences:

ƒ

Death or serious injury

Protective measures:

ƒ

If protection against accidental contact is required for the control terminals
of the controller and the connections of the plugged device modules, ...
– a double isolating distance must exist.
– the components to be connected must be provided with the second

isolating distance.

E82ZAFVC001
function module

Protective insulation between bus and ...

Type of insulation (acc. to EN 61800−5−1)

l

reference earth / PE (X3/SH)

Functional insulation

l

external supply (X3/V+)

No electrical isolation

l

supply for CINH (X3/20)

No electrical isolation

l

controller inhibit, CINH (X3/28)

Functional insulation

l

power section

– 8200 vector

Reinforced insulation

– 8200 motec

Reinforced insulation

– starttec

Reinforced insulation

l

control terminals

– 8200 vector

Functional insulation

– 8200 motec

Functional insulation

E82ZAFVC010
function module

Protective insulation between bus and ...

Type of insulation

l

Reference earth / PE (X3.1/SH)

Functional insulation

l

External supply (X3.1/V+)

No functional insulation

l

Supply for CINH (X3.2/20)

No functional insulation

l

Controller inhibit, CINH (X3.2/28)

Functional insulation

l

8200 vectorpower unit

Double insulation

l

8200 vector control terminals

Functional insulation