Electrical installation
Wiring with a host (master)

5

l

22

EDS82ZAFVCxxx EN 4.0

Properties of the "Thick Cable" in accordance with DeviceNet specification

General features

Structure

Two shielded balanced lines, common axis with drain wire in the centre

Total shielding

65% coverage
AWG 36 (at least 0.12 mm) of tin−coated copper braid (individually tinned)

Drain wire

At least copper 18; at least 19 cores (individually tinned)

Outer diameter

10.41 ... 12.45 mm

Concentricity

The radius deviation has to be within 15 % of half the outside diameter.

Cable sheath labelling

Name of vendor, part no., and additional labelling

Spec. DC resistance (braid, wrapping, leakage)

5.74

W/km (nom. up to 20 °C)

Certifications (U.S. and Canada)

NEC (UL), CL2/CL3 (min.)

Bend radius

20 x diameter (installation) / 7 x diameter (fixed)

Ambient temperature (operation)

−20 ... +60 °C at 8 amperes;
linear current derating to zero at 80 °C

Storage temperature

−40 ... +85 °C

Pull tension

845.5 N

max

Features of the data line

Conductor pair

At least copper 18; at least 19 cores (individually tinned)

Insulation diameter

3.81 mm (nom.)

Colours

Light blue, white

Pair windings / m

Approx. 10

Shielding/conductor pair

2000/1000, Al/Mylar, Al side on the outside, w/shorting fold (for tensile load)

Impedance

120

W +/− 10 % at 1 MHz

Capacitance between conductors

39.37 pF/m at 1 kHz (nom.)

Capacitance between one conductor and another which is
connected to the shield.

78.74 pF/m at 1 kHz (nom.)

Capacitive assymetry

3937 pF/km at 1 kHz (nom.)

Spec. DC resistance at 20 °C

22.64

W/km (max.)

Damping

0.43 dB/100 m at 125 kHz (max.)
0.82 dB/100 m at 500 kHz (max.)
1.31 dB/100 m at 1.00 MHz (max.)

Features of the voltage line

Conductor pair

At least copper 15; at least 19 cores (individually tinned)

Insulation diameter

2.49 mm (nom.)

Colours

Red / black

Pair windings / m

Approx. 10

Shielding/conductor pair

1000/1000, Al/Mylar, Al side on the outside, with w/shorting fold (for tensile load)

Spec. DC resistance at 20 °C

11.81

W/km (max.)

Properties of the "Thin Cable" in accordance with DeviceNet specification

General features

Structure

Two shielded balanced lines, common axis with drain wire in the centre

Total shielding

65% coverage
AWG 36 (at least 0.12 mm) of tin−coated copper braid (individually tinned)

Drain wire

At least copper 22; at least 19 cores (individually tinned)

Outer diameter

6.096 ... 7.112 mm

Concentricity

The radius deviation has to be within 20 % of half the outside diameter.

Cable sheath labelling

Name of vendor, part no., and additional labelling

Spec. DC resistance (braid, wrapping, leakage)

10.5

W/km (nom. at 20 °C)

Certifications (U.S. and Canada)

NEC (UL), CL2 (min.)

Bend radius

20 x diameter (installation) / 7 x diameter (fixed)

Ambient temperature (operation)

−20 ... +70 °C at 1.5 amperes;
linear current derating to zero at 80 °C

Storage temperature

−40 ... +85°C

Pull tension

289.23 N

max