Installation, Electrical installation terminal assignment – Lenze E82ZAFVC010 User Manual

Page 26

Advertising
background image

Installation

Electrical installation
Terminal assignment

5

l

26

EDS82ZAFVCxxx EN 4.0

Function module E82ZAFVC010

Controller inhibit (CINH) supply via internal voltage source

GND1

V+

20

CH

CL SH

28

39

7

GND2

X3.1

X3.2

V-

_

+

E82ZAFD110

Controller inhibit (CINH) supply via external voltage source

GND1

V+

20

CH

CL SH

28

39

7

GND2

X3.1

X3.2

V-

_

+

_

+

E82ZAFD112

Min. wiring required for operation

X3.1/

Designation

Function

Level

V−

Reference potential for external supplyvoltage

CL

CAN−LOW

CAN data line (LOW)

SH

SHIELD

Shield

CH

CAN−HIGH

CAN data line (HIGH)

V+

External supply voltage

Please see the notes for external
supply voltage!

X3.2/

Designation

Function

Level

7

GND1

Reference potential for X3.2/20

39

GND2

Reference potential for controller inhibit (CINH) at X3.2/28

28

CINH

Controller inhibit

l

Start = HIGH (+12 V ... +30 V)

l

Stop = LOW (0 ... +3 V)

20

DC voltage source for internal supply of
controller inhibit (CINH)

+20 V (ref.: GND1)

Advertising