6 bus cable length, 7 use of plug connectors, Bus cable length – Lenze E82ZAFVC010 User Manual

Page 28: Use of plug connectors, Installation, Stop

Advertising
background image

Installation

Electrical installation
Bus cable length

5

l

28

EDS82ZAFVCxxx EN 4.0

5.2.6

Bus cable length

Depending on the baud rate and the cable type used (thick cable/thin cable), the following
bus cable lengths are possible:

Baud rate [kbps]

Bus cable lengths [m]

Thick cable

Thin cable

125

500

100

250

250

500

100

If both thick and thin cable types are used, the maximum cable lengths can be defined
according to the baud rates as follows:

Baud rate [kbps]

Max. bus cable length

125

500 m = L

thick

+ 5 L

thin

250

250 m = L

thick

+ 2.5 L

thin

500

100 m = L

thick

+ L

thin

L

thick

: thick cable length

L

thin

: thin cable length

)

Note!

Select a baud rate in dependency of the data volume, cycle time and number
of nodes just high enough to suit your application.

5.2.7

Use of plug connectors

(

Stop!

Observe the following to prevent any damage to plug connectors and
contacts:

ƒ

Only pug in / unplug the plug connectors when the controller is
disconnected from the mains.

ƒ

Wire the plug connectors before plugging them in.

ƒ

Unused plug connectors must also be plugged in.

Use of plug connectors with spring connection