Data transfer

9

l

54

EDS82ZAFVCxxx EN 4.0

Two different telegram types are transferred between master computer and controller(s):

ƒ

I/O data

ƒ

Explicit messages

As indicated in the table, these telegram types are subdivided into communication
channels according to their time−critical response:

Communication channel

Telegram type

à

Parameter data channel

à

Explicit messages

Explicit messages are used for configuration and parameter setting
of the devices connected to the DeviceNet. The relationship
between two devices is a client−server relationship. The client
sends the request and the server accepts the order and tries to
settle it. The server reacts as follows

l

the required data in case of a positive response or

l

a fault message in case of a negative response.

l

Enables the access to all Lenze codes.

l

Automatic storage after a change of
frequency inverter parameters:
– 8200 vector
– 8200 motec

à

Process data channel
– You can control the controller using

the I/O data.

– The master computer can directly

access the I/O data. The data is
directly stored into the I/O area of the
PLC.

– I/O data is not stored in the controller,

they are cyclically transferred
between the host and the controllers
(continuous exchange of input and
output data).

à

I/O data

I/O Data (process data) is transmitted/received according to the
producer/consumer principle, i. e. there is one transmitter and no
or an arbitrary number of receivers.
The following transmission modes are supported:

l

I/O polled messages (polled)
– The Poll command being transmitted from the master,

includes output data for the slave. The slave then transmits
its input data to the master.

l

Cyclic I/O
– With cyclic I/O, master and slave create data independently of

each other which are sent according to the settings of a
timer. The user must set the timer.

l

Change of State (COS)
– This type of I/O message is a special cyclic message. COS

nodes send their data when the data status is changed.

)

Note!

The default message service for the E82ZAFVC function module is the I/O
polled message. Other services can be released by means of a DeviceNet
Manager tool.