Installation

Mechanical installation
Wiring according to EMC (CE−typical drive system)

5

l

20

EDS82ZAFVCxxx EN 4.0

5

Installation

}

Danger!

Inappropriate handling of the function module and the standard device can
cause serious injuries to persons and damage to material assets.
Observe the safety instructions and residual hazards included in the
documentation of the standard device.

(

Stop!

The device contains components that can be destroyed by electrostatic
discharge!
Before working on the device, the personnel must ensure that they are free of
electrostatic charge by using appropriate measures.

5.1

Mechanical installation

Follow the notes given in the Mounting Instructions for the standard device for the
mechanical installation of the function module.

The Mounting Instructions for the standard device ...

ƒ

are part of the scope of supply and are enclosed with each device.

ƒ

provide tips to avoid damage provide tips to avoid damage through improper
handling.

ƒ

describe the obligatory order of installation steps.

5.2

Electrical installation

5.2.1

Wiring according to EMC (CE−typical drive system)

For wiring according to EMC requirements observe the following points:

)

Note!

ƒ

Separate control cables/data lines from motor cables.

ƒ

Connect the shields of control cables/data lines at both ends in the case of
digital signals.

ƒ

Use an equalizing conductor with a cross−section of at least 16 mm

2

(reference: PE) to avoid potential differences between the bus nodes.

ƒ

Observe the other notes concerning EMC−compliant wiring given in the
documentation for the standard device.