Codes 8, C1510: configuration of process input data – Lenze E82ZAFVC010 User Manual

Page 41

Advertising
background image

Codes

8

l

41

EDS82ZAFVCxxx EN 4.0

C1510:
Configuration of process input data

Code

Subcode

Possible settings

Data type

Lenze

Selection

C1510

FIX32

1 (PEW1)

1

See table below

2 (PEW2)

3

3 (PEW3)

4

4 (PEW 4)

5

5 (PEW 5)

6

6 (PEW 6)

7

7 (PEW 7)

8

8 (PEW 8)

9

9 (PEW 9)

10

10 (PEW 10)

11

11 (PEW11)

12

12 (PEW12)

13

The assignment of the bit status information or the actual values of the controller to the
max. 12 process data input words (PEW) of the master can be freely configured.

Selection

Scaling

1

FIF status word 1 (FIF−STAT1)

16 bits

2

FIF status word 2 (FIF−STAT2)

16 bits

3

Output frequency with slip (MCTRL1−NOUT+SLIP)

±24000

º ±480 Hz

4

Output frequency without slip (MCTRL1−NOUT)

±24000

º ±480 Hz

5

Apparent motor current (MCTRL1−IMOT)

2

14

º 100 % rated device current

6

Actual process controller value (PCTRL1−ACT)

±24000

º ±480 Hz

7

Process controller setpoint (PCTRL1−SET)

±24000

º ±480 Hz

8

Process controller output (PCTRL1−OUT)

±24000

º ±480 Hz

9

Controller load (MCTRL1−MOUT)

±2

14

º ±100 % rated motor torque

10

DC−bus voltage (MCTRL1−DCVOLT)

16383

º 565 VDC at 400 V mains

16383

º 325 VDC at 230 V mains

11

Ramp function generator input (NSET1−RFG1−IN)

±24000

º ±480 Hz

12

Ramp function generator output (NSET1−NOUT)

±24000

º ±480 Hz

13

FIF−OUT.W1

16 bits or 0 ... 65535

14

FIF−OUT.W2

16 bits or 0 ... 65535

15

FIF−OUT.W3

0 ... 65535

16

FIF−OUT.W4

0 ... 65535

)

Note!

ƒ

FIF−OUT.W1 is digitally defined in the Lenze setting and assigned with the
16 bits of the controller status word 1 (C0417).

ƒ

Before you assign an analog signal source (C0421/3

¹ 255), the digital

assignment must be deleted (C0417/x = 255)! Otherwise the output signal
would be incorrect.