Commissioning – Lenze E82ZAFVC010 User Manual

Page 30

Advertising
background image

Commissioning

Commissioning steps

6

l

30

EDS82ZAFVCxxx EN 4.0

Step

Procedure

see

1.

If necessary, set the software compatibility

^ 31

2.

Set the node address

3.

Set the baud rate

4.

Inhibit the standard device via terminal 28 (CINH).

Terminal 28 on LOW potential.
The standard device can be inhibited and enabled via the bus

Manual of the
standard device

5.

Connect mains voltage

6.

Connect the separate voltage supply for the function module
(Switch on the DeviceNet).

^ 24

Response of the front LED display:
Directly after the voltage supply for the function module has been connected, both
LEDs at the front light up for a short time in the following order:

l

The LED Status of connection with bus" changes its colour from green to red
before it goes off.

l

The LED "Status of the connection to the standard device" changes its colour
from green to red before it goes off.

l

The LED Connection status to the bus" at the front of the function module is
blinking (only visible in case of 8200 vector).

l

The green LED Status of connection with standard device" at the front of the
function module is on (only visible in case of 8200 vector).

l

Keypad:

dc(if attached)

^ 34

7.

Configure the host system for communicating with the function module with
configuration software:

l

With explicit messages" all parameters can be read or written from the drive
and/or function module.

l

Actual values can be read (e.g. status word) or setpoints can be written (e.g.
frequency setpoint) via the I/O data.

Response

l

The LED Status of connection with the bus" at the front of the function module
changes from blinking to the constantly ON state.

8.

Configure process data channel of the standard device (see "application range") for
operation with the function module.

Recommendation
Set code C0005 = 200 after the Lenze setting has been loaded (C0002).
C0005 = 200 preconfigures the device for the operation with a function module.
Control and status words are already linked.

Continue with step 12.

Manual of the
standard device

9.

If required, assign the process output data of the master/scanner via C1511 to the
input signals of the standard device.

^ 44

10.

If required, assign the process input words of the master/scanner to the output
signals of the standard device via C1510.

^ 41

11.

If the configuration in step 9. or step 10. has been changed:
Enable process output data with C1512 = 65535.

^ 47

12.

Enable standard device with terminal 28 (CINH) (terminal 28 on HIGH).

13.

Send setpoint via a selected process data output word.
The drive is now running.

14.

Inhibit the standard device via the bus (e.g. control word bit 9) or terminal 28 (CINH).

Advertising