Codes

8

l

47

EDS82ZAFVCxxx EN 4.0

C1512:
I/O data enable

Code

Subcode

Possible settings

Data type

Lenze

Selection

C1512 **

65535

0

[1]

65535

FIX32

If C1511 is changed, the process output data is automatically inhibited to ensure data
consistency.

Use the decimal value in code C1512 to enable some or all process output words (PAW)
again:

ƒ

0 = Inhibit PAW

ƒ

1 = Enable PAW

Bit 15 ... 12

Bit 11

Bit 10

...

Bit 1

Bit 0

reserved

PAW12

PAW 11

...

POW2

PAW 1

The bit settings 0 to 11 are each assigned to a process data word. The bit settings 12 to 15
are reserved.

Use the value 65535 (FFFF

hex

) in code C1512 to release all process output data.

)

Note!

ƒ

The release is required if the process output data configuration has been
changed.

C1516:
Baud rate setting

Code

Subcode

Possible settings

Data type

Lenze

Selection

C1516

0

see below

FIX32

Selection

Baud rate

0

125 kbits/s

1

250 kbits/s

2

500 kbits/s

255

Auto baud (automatic baud rate recognition)

Only valid if switches S7 and S8 are in the ON position.

)

Note!

Switch off the voltage supply of the function module and then on again to
activate changed settings of the baud rate.