7 diagnostics, 1 led status displays, Diagnostics – Lenze E82ZAFVC010 User Manual

Page 34: Led status displays, 7diagnostics

Advertising
background image

Diagnostics

LED status displays

7

l

34

EDS82ZAFVCxxx EN 4.0

7

Diagnostics

7.1

LED status displays

Function module E82ZAFVC001

Function module E82ZAFVC010

E82ZAFD001A*

E82ZAFD101A*

Pos

Colour

Status

Notes

1

off

Function module is not supplied with voltage,
external voltage supply is switched off

green

blinking

Function module is supplied with voltage but not connected to the controller.
Reason:
Standard device is

l

switched off

l

is being initialised

l

not available

on

Function module is supplied with voltage and is connected to the standard
device

red

blinking

Internal error, Lenze setting has been loaded

on

Internal error of the function module

2

off

l

No connection to the master

l

Function module is not supplied with voltage.

green

blinking

Dup_Mac_ID" test phase. Not yet connected to master (scanner).

on

DeviceNet connection established.

red

blinking

No communication due to time−out

on

Critical bus error