Installation – Lenze E82ZAFVC010 User Manual

Page 23

Advertising
background image

Installation

Electrical installation

Wiring with a host (master)

5

l

23

EDS82ZAFVCxxx EN 4.0

Features of the data line

Insulation diameter

1.96 mm (nom.)

Conductor pair

At least copper 24; at least 19 cores (individually tinned)

Colours

Light blue, white

Pair windings / m

Approx. 16

Shielding/conductor pair

1000/1000, Al/Mylar, Al side on the outside, with w/shorting fold (for tensile load)

Impedance

120

W +/− 10 % at 1 MHz

Runtime

4.46 ns/m (max.)

Capacitance between conductors

39.37 pF/m at 1 kHz (nom.)

Capacitance between one conductor and another which is
connected to the shield.

78.74 pF/m at 1 kHz (nom.)

Capacitive assymetry

3.94 pF/km at 1 kHz (max.)

Spec. DC resistance at 20 °C

91.86

W/km (max.)

Damping

0.95 dB/100 m at 125 kHz (max.)
1.64 dB/100 m at 500 kHz (max.)
2.30 dB/100 m at 1.00 MHz (max.)

Features of the voltage line

Conductor pair

At least copper 22; at least 19 cores (individually tinned)

Insulation diameter

1.4 mm (nominal)

Colours

Red, black

Pair windings / m

Approx. 16

Shielding/conductor pair

1000/1000, Al/Mylar, Al side on the outside, with w/shorting fold (for tensile load)

Spec. DC resistance at 20 °C

57.41

W/km (max.)

Advertising