Appendix – Lenze E82ZAFVC010 User Manual

Page 63

Advertising
background image

Appendix

Data transfer

Overview of the implemented objects for the function module

9

l

63

EDS82ZAFVCxxx EN 4.0

Manufacturer−specific class 100 (64

hex

):

Access to Lenze codes

)

Note!

We recommend the use of class 110 (

65).

Instance 0:

Attribute

Service(s)

Description

Data type

Value

1

GET

Revision

UINT

0001

hex

Instance 1:

Attribute

Service(s)

Description

Data type

Value

1

GET/SET

Explicit Message
Lenze Codes

See table below

Dependent on order

Data type instance 1

Byte

Request

Response

1

Code Low

Code Low

2

Code High

Code High

3

Subcode

Subcode

4

Reserve

Status

l

Value of byte = 0: The message does not contain any faults.

l

Value of the byte

¹0: Message is faulty.

The value of the byte indicates the fault number (for
explanation see the following table).

5
..
..

Data_1 Low

Data_1 Low

Data_1 High

Data_1 High

..

..

..

..

Data_22 Low

Data_22 Low

Data_22 High

Data_22 High

Explanation of the fault number:

Error code

Explanation

03

hex

Invalid data type

04

hex

Subcode no. not accepted

05

hex

Code no. not accepted

07

hex

No right to access due to operating state

08

hex

No right to access due to operating mode

09

hex

No right to access as parameters are only readable

0A

hex

No general right to access

0B

hex

Data block too long

0C

hex

Collisions with other value ranges

0D

hex

Quit value range

0E

hex

Fault − general value range

2X

hex

Fault − AIF interface

FF

hex

General fault

Services:

Service code

Name

Description

0E

hex

Get_Attribute_Single

Reading an attribute

10

hex

Set_Attribute_Single

Writing of an attribute

Advertising