User interface, Stop – Lenze 931W User Manual

Page 17

Advertising
background image

User interface

Introduction

Menu bar

4

17

HB 13.0001-EN

3.0

Description

Menu bar
Save

If this function is selected, all changes that have been carried out on the

current menu page are saved. This function is provided in the online status

as well as in the offline status. If the function is carried out online, all

changes are written into the read-only memory of the drive, so that they

still remain stored in case of a mains failure. This function should not be

mixed up with the function ”Save configuration”, which in contrast to

”Save” stores an image of the drive data in file format on a data medium of

the PC.

Restoring the default setting

z

Service

– Reset service data

z

Fieldbus

– Reset fieldbus settings (CANopen or Profibus objects)

z

System

– Reset system settings

z

Controller

– Reset controller parameters

z

Current travel data set

– Only reset current travel data set

z

All travel data sets

– Reset all travel data sets

z

intelliBox

– Reset inputs/outputs

z

Reference

– Reset reference run

The selection has to be acknowledged afterwards.

Stop!

If the setting of the ”Service” tab is reset, among other things the current

factor and the resolver offset are overwritten.
In this case the drive might have to be dismounted and the resolver might

have to be readjusted in the loadfree state, as the resolver adjustment has to

be carried out individually for each motor and cannot be adopted even for a

motor of the same type. If the resolver offset is set incorrectly, the motor

cannot operate.