Software implementation and parameter setting

Inputs and outputs menu

Application Box: digital inputs

5

56

HB 13.0001-EN 3.0

The following functions can be assigned to the freely configurable digital input:

Function

Control via ”Fluxx” or via digital IOs

Control via CAN bus

Control via Profibus

Unused

No function

No function

No function

Reference (reference

switch)

In the case of the reference type ”Edge” or ”Reference switch”, the digital input is evaluated as a reference

switch. When a reference run is effected and the reference switch is reached, the home position is set in

consideration of the settings carried out on the ”Reference” tab.

Output stage off

The output stage of the inverter is switched off if this input

is activated, while the electronics/control is supplied further

on. If the motor is running at the time of activation, it will

coast in an uncontrolled manner after the output stage has

been switched off. There is no actively injected torque

available on the motor shaft.

After deactivation of the input, the drive can be restarted.

No function

No function

Reference window

No function

No function

No function

Start reference run

The reference run which is specified in the ”Reference”

menu and which serves to the protective multiple earthing

of the drive or to define all absolute position values is

started when transition to the active status takes place, if

the drive has not yet been referenced beforehand. A second

referencing cannot be started via the input. For this

purpose, the digital input is to be selected as ”Reference

start” in the ”Reference” tab.

No function

No function

Goto 99

If the input is activated, the current travel data set is interrupted immediately, and the travel data set 99 is

selected or started.

Synchronisation

For synchronising several drive systems, the

”Synchronisation” function can be used. The term

”synchronisation” in this connection refers to the

simultaneous start of several drive systems. For this

purpose it is required to specify the number of the next

travel data set with a negative sign in the field ”Next travel

data set”. If, for instance, in the case of a linkage between

travel data sets, the travel set data number is entered in the

field ”Next travel data set” with a negative sign (e.g. -5 for

the fifth travel data set), the subsequent travel data set is

only started if the input is active.

No function

No function

Stopover

The current travel program is stopped if the input is active,

and the drive is decelerated to the speed 0. The output

stage remains active during stopover. As soon as the input

is deactivated, the program or the current travel data set is

continued.

No function

No function

Single step mode

In the case of a linkage of travel data sets, the subsequent

travel data set only is started if the input is active.

No function

No function

Teach

By means of the ”Teach” function, the current actual

position of the drive can automatically be transmitted as a

set position of the travel data set 0 under the following

conditions:

A The controller type of travel data set 0 is ”Absolute

position”

B The output stage has to be switched off (motor at zero

current)

This function can only be used in the operating modes

”Online level 1” or ”Offline” of the Fluxx program.

No function

No function

Stopover at zero

current

The current travel program is stopped if the input is active,

and the drive is decelerated to the speed 0. Afterwards the

output stage is switched off (motor at zero current). As soon

as the input is deactivated, the output stage is activated,

and the program or the current travel data set is continued.

No function

No function

Tab. 6

Freely configurable input