Software implementation and parameter setting

Service menu

Software version

5

31

HB 13.0001-EN

3.0

Resolver offset
By orientating the resolver, the angle which is stored as the offset angle of the

motor-resolver combination in the axis controller can be calculated according to the

number of motor and resolver pole pairs. The value that is determined is considered with

regard to the rotary field generation and is device-defined. In case of operating errors or

replacement of the electronics, it can also be re-entered manually. See also chapter

”Resolver adjustment”.

Resolver adjustment
By using this button, the resolver is adjusted, which is a calculation of the angle between

the rotary field indicator and resolver indicator in increments and a software adjustment.

In doing this, the motor axis is gradually moved for adjustment.

Note!

For adjusting the resolver, the motor has to be in a load-free state, which for a

required resolver adjustment could possibly require a dismounting of the

motor from an existing system.

As the resolver adjustment is already effected ex works, this button as far as possible

should not be used. Particular care is to be taken when loading a configuration in the

service mode - for this, see also the chapter ”Menu bar” ( 16).

Current controller response time
The current controller response time describes the adjustable value of the phase shift

between motor current and motor voltage. The current controller response time serves to

compensate the phase shift of the current caused by the motor inductance. The following

effects can be derived from the amount of the value that is set here:

0 μs

No effect

200 - 600 μs

The current is applied so that the phase shift caused by the inductance is compensated by

the current controller response time selected. The current controller response time is to be

determined in a speed-dependent and torque-dependent manner.

Value too high

In case of settings that are too high, the motor utilisation is degraded, which can be seen by a

no-load current and rated current that that is too high.

As astandard value, asetting of 250 to 350 μs (basic setting:350 μs)is recommended. Only

for very high motor inductances, a higher setting of the current controller response time

is reasonable.

5.3.2

Software version

Via this field, the firmware version of the motor can be viewed. This information, as well

as the device identification, is also important for issues of support. Furthermore the

firmware version determines the function. For the use on the Profibus-DP or CAN bus there

are different firmware versions. In case of doubt, however, the Lenze support hotline

should be notified.

5.3.3

Operating hours

Here the operating hours of the inverter that have already beenachieved are entered inthe

format of hours: minutes.