Software implementation and parameter setting

Reference menu

Reference type

5

69

HB 13.0001-EN

3.0

The different possibilities resulting therefrom are demonstrated by 2 examples, which can

begatheredfromthe followingillustration. Theexamples referto alinear motion,defining

the ”positive direction” on the right side. In both cases, referencing is carried out to the

right limit switch (”Active high”).

Reference type ”Limit switch, right”, positive

reference speed

Reference type ”Limit switch, right”, negative

reference speed

Example 1

Example 2

Limit switch signal level

V

reference

Position

Edge

Starting point

Limit switch

Fig. 7

Reference run to a limit switch

Example 1: A positive reference speed is to be set. The drive is traversed until the edge of

the limit switch is recognised. If the limit switch is entered, homing is carried out on this

edge.
Example 2: A negative reference speed is to be set. In this case, the drive decelerates its

speed to standstill when entering the limit switch and afterwards accelerates in the oppo-

site direction. Homing is carried out on the falling edge of the limit switch, which sets itself

when the limit switch is left.

End stop, left/right
Apart from referencing to a reference signal it is possible to select a mechanical limit stop

as a home position. In this connection, a mechanical limit stop is recognised in an

inverter-internal manner by means of the evaluation of the actual speed value and the

reference torque. If, in spite of the available reference torque no change in position is

effected for a period of 0.5 s (actual speed ~ 0), the mechanical limit stop is considered as

recognised. The home position is set in this position.
The direction in which the mechanical limit stop is searched for is specified by the sign of

the reference speed. In order to avoid damages on the mechanics or in the drive train, it is

recommended for this reference run to select the reference torque below the rated torque

of the drive.
If gearboxes are used and a greater output torque results from this, a reference run on an

end stop has to be checked thoroughly. In the case of an incorrect dimensioning, the limit

stops or the gearbox may suffer damage.