ƒ

Explanations of individual trigger conditions

Warning

If a warning signal occurs, a triggering process is effected, however, not yet

resulting in a switch-off of the motor.

Example: motor temperature > 130°C

Fault

If a fault message occurs, a triggering process is effected, resulting in the

switch-off of the motor

Example: motor temperature > 140°C

Editing data set

Recording is effected as soon as a travel data set is edited.

Setpoint reached

Here recording is effected from the time when the setpoint specified in the

current travel data set has been reached. The type of setpoint depends on the

controller type, e. g. ”Speed”.

Reference run active

Triggering the activation of the reference run.

Drive in standstill

As soon as the drive is in standstill, i.e. speed=0 rpm, triggering is effected.

Profibus active

In this case, recording is carried out if the Profibus is activated, e.g. for the

communication start of the motor as a DP slave with the master.

System error

Triggering to system errors, i. e. the amount of the system deviation is greater

than the value specified in the following error window of the ”Controller”

menu. Additionally, the torque on the motor shaft has reached its maximum

value.

Motor deenergised

The output stage is switched off, i. e. a torque is no longer available on the

motor shaft.

Stopover

Triggering to a stopover which is characterised by an interrupted travel data set.

The command for a stopover can be effected via the motor input (see ”Digital

input/output” menu).

Single step mode

Here recording is effected if the motor is in single step mode. The single step

mode can be activated by selecting ”Single step~On” in the upper menu bar of

the user program.

Single step pause

The pause in single step mode is triggered, which eventually is effected

automatically after completion of a travel data set in single step mode. The

start of the next travel data set is either carried out by a new start command

(Single step~Continue) in the service program, or via the motor input that is

configured by ”Single step”.

Reference set

As soon as the reference is set, recording can be carried out. This happens after

a reference run has been completed. The reference furthermore is set if no

reference run has been set in the ”Reference” menu.

Reading
The data of the recording buffered in the inverter are transmitted to the PC via the serial

interface. In order to accomplish this function, the trigger must have been activated

beforehand, and then the corresponding trigger condition has to be met, e. g. the start of

a specific travel data set.