Communication Chapter 4
The next example shows the message configuration for a CIP Generic
message type. A CIP Generic message can read or write data,
depending on the Service Type you specify.
Refer to DeviceNet Class Services on
page 102
.
In this example, the ControlLogix reads the User-configured Data
Table into tag dataPM3K_User(0), configured as an array of 23
elements of Real type.
ControlLogix Controller CIP Generic Messaging Example
This example uses the following message parameter values:
•
Service Type: Get_Attribute_Single, (service code oe hex)
•
Object class: 4 (hex), Assembly
•
Instance: 37 (decimal), User configured table results
•
Attribute: 3 (hex), Data