Publication 1404-UM001F-EN-P - November 2009

109

Communication Chapter 4

The next example shows the message configuration for a CIP Generic
message type. A CIP Generic message can read or write data,
depending on the Service Type you specify.

Refer to DeviceNet Class Services on

page 102

.

In this example, the ControlLogix reads the User-configured Data
Table into tag dataPM3K_User(0), configured as an array of 23
elements of Real type.

ControlLogix Controller CIP Generic Messaging Example

This example uses the following message parameter values:

Service Type: Get_Attribute_Single, (service code oe hex)

Object class: 4 (hex), Assembly

Instance: 37 (decimal), User configured table results

Attribute: 3 (hex), Data