General specifications – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 339

Advertising
background image

Publication 1404-UM001F-EN-P - November 2009

339

Technical Specifications Appendix D

General Specifications

Dielectric Withstand

Control Power

2000V

Voltage Inputs

2000V

Current Inputs

2000V

Status Inputs

500V

Control Relays

1600V

Terminal Blocks

Power Supply and Voltage input
Terminals

4 mm

2

(12 AWG) max,

1.02 Nm (9 lb-in) Torque.,
75 °C (167 °F) or Higher Copper Wire only

Relay, KYZ outputs, Current input
terminals

(1)

2.5 mm

2

(14 AWG) max, 1.18 Nm (10.4 lb-in) Torque

75 °C (167 °F) or Higher Copper Wire only

Status inputs, RS485

2.5 mm

2

(14 AWG) max

0.56 Nm (5 lb-in) Torque

RIO, DNT (When present)

2.5 mm

2

(14 AWG) max

0.56 Nm (5 lb-in) Torque

Temperature, Operating

-20…60 °C (-40…140 °F) Cat. No. 1404-DM, 1404-Mxxxx-000, 1404-Mxxxx-DNT
0…55 °C (32…131 °F) 1404-Mxxxx-232, -RIO, -ENT, -CNT

Temperature, Storage

-40…85 °C (-40…185 °F)

Humidity

5…95%, Noncondensing

Vibration

10…500 Hz: 2 g Operational (±0.012 in.)

Shock

1/2 Sine Pulse, 11 ms duration: 30 g Operational and 30 g Nonoperational

(1)

Recommended Ring lug: AMP part # 320634.