Powermonitor 3000 Data Tables Appendix A

Setpoint Setup/Read-back Select and Status Parameters

CSP File No.

N23

Remote I/O BT

22

CIP Assy. Inst.

24 (Write), 25 (Read)

No. of Elements

16

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

All

Setpoint Setup/Read-back Select and Status

Element
No.

Modbus
Address

Element name

Range

Units

Default
Value

Comment

0

40701

Password

0…9999

-

0

Required for configuration, -1 for readback
select, returns -1.

1

40702

Setpoint number

1…10 (M4, M5)
1…20 (M6, M8)

-

-

Refer to Writing Setpoint Configuration by
Using Communication on page 134

.

2

40703

Read-back mode

0…1

-

0

3

40704

Setpoint type

0…52

-

0

(1)

4

40705

Evaluation condition 0…5

-

0

5

40706

High limit
Integer

0…9999

Depends
on
setpoint
type

0

(1)

6

40707

High limit Exponent

-4…21

0

(1)

7

40708

Low limit

Integer

0…9999

0

(1)

8

40709

Low Limit Exponent

-4…21

0

(1)

9

40710

Action delay

0…3600 (M4, M5)
0…30,000
(M6, M8)

Seconds
(M4, M5)
0.1 s
(M6, M8)

0

10

40711

Release delay

0…3600 (M4, M5)
0…30,000
(M6, M8)

Seconds
(M4, M5)
0.1 s
(M6, M8)

0

11

40712

Output action

0…32 (M4, M5)
0…43 (M6, M8)

-

0

(1)

12

40713

Status

0…1

-

0