Device configurations summary, Refer to the device configurations summary tab, Advanced device configuration – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 50

Advertising
background image

50

Publication 1404-UM001F-EN-P - November 2009

Chapter 3 Powermonitor 3000 Unit Operations

Advanced Device Configuration

A number of parameters are grouped into Advanced Configuration,
including the Password, demand and projected demand setup, relay
and KYZ pulse operation setup, metering accuracy options, date/time
and display module scrolling rate. To perform advanced configuration
by using the display module, navigate through these menus: PROG. >
PASS? > CONFIGURATION > ADVANCED. You may also set the
advanced device configuration via communication by writing to the

Advanced Device Configuration

table.

Password

The password protects the unit against unauthorized commands or
configuration changes. Be sure to write down the new password and
keep it in a safe place. Range 0…9999, default 0000.

TIP

If you forget or lose your password, contact Rockwell Automation
Technical Support for assistance.

Refer to Rockwell Automation

Support

on the back cover of this manual.

Device Configurations Summary

Parameter Range

Default

User

Setting

Basic

Configuration

Wiring Mode

0 = Delta 3 CT
1 = Delta 2 CT
2 = Direct Delta 3 CT
3 = Direct Delta 2 CT
4 = Open Delta 3 CT

5 = Open Delta 2 CT
6 = Wye
7 = Single Phase
8 = Demo

6 = Wye

PT Primary

1

10,000,000

480

PT Secondary

1

600

480

CT Primary

1

10,000,000

5

CT Secondary

1

5

5

I4 Primary

1

10,000,000

5

I4 Secondary

1

5

5

Nominal System Voltage
(M6 and M8 only)

1

10,000,000

480