Write error status parameters, Write error status, Table – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 236

236
Publication 1404-UM001F-EN-P - November 2009
Appendix A Powermonitor 3000 Data Tables
Write Error Status Parameters
CSP File No.
N32
Remote I/O BT
4
CIP Assy. Inst.
38
No. of Elements
2
User Configurable No
Data Type
Integer
Data Access
Read only
PM3000 Type
All
Write Error Status
Element
No.
Modbus
Address
Element Name
Range
Default
Value
Comment
0
31101
File, instance or BT
number
-
-
Identifies data table written to last, value depends on comms
type. For Modbus, starting address of table written to last.
1
31102
Offending Element
-1 = Last write was successful
0…26 = first unacceptable element of unsuccessful write
For Remote I/O Only:
0 = Last write was successful
1…27 = First unacceptable word of unsuccessful write
For Modbus Only:
-1 = Last write was successful
40,001…42,001 - first unacceptable address of unsuccessful
write.