325

Sample Applications Appendix C

0002

N9:11

0

Allow Write

EQU

Equal
Source A

N9:6

8<

Source B

4

4<

EQU

EQU

Equal
Source A

N9:6

8<

Source B

52

52 <

EQU

JSR

Jump To Subroutine
SBR File Number

U:4

JSR

When a write of a float file is being performed it is necessary to swap the words in teh float file before sending the write request.
This is only necessary for Instance 4 or Instance 52.

0003

N9:11

0

Allow Write

B3:0

0

Message Pending

FLL

Fill File
Source

0

Dest

#N7:0

Length

65

FLL

COP

Copy File
Source

#N9:0

Dest

#N7:0

Length

10

COP

COP

Copy File
Source

#N14:0

Dest

#N7:10

Length

64

COP

COP

Copy File
Source

#N7:10

Dest

#M0:3.1100

Length

65

COP

L

N7:0

15

Enable Transfer Bit

COP

Copy File
Source

#N7:0

Dest

#M0:3.1000

Length

10

COP

L

B3:0

0

Message Pending

Allow the scanner to write to the power monitor. Put the new integer configuration data in N14 starting at location 0. Put the configuration
if it is of float type in file F13 starting with word 0. Enter the rest of the CIP message information needed for transfer in N9 starting with
word 0. The process is similar to the request of information except that the size in words of the data to write is to appear in N7:9 and the
service to be performed is changed.

Advertising