Appendix C Sample Applications

MicroLogix Controller and EtherNet/IP Communication Networks

This example reads and writes the power monitor date and time table
by using a MicroLogix 1400 controller and EtherNet/IP
communication.

MicroLogix Controller Ethernet Port Setup

Assign the MicroLogix controller and the power monitor compatible
network addresses. In this example the power monitor IP address is
10.90.172.91 and the ML1400 IP address is 10.90.172.95.

IMPORTANT

If you are using RSLinx Classic software as your OPC software, a
licensed RSLinx OEM or higher version is required.

IMPORTANT

The power monitor master module firmware must be 4.x or later and
the Ethernet protocol must be set to CIP or CSP/CIP to support
communication with a MicroLogix controller.