Powermonitor 3000 Data Tables Appendix A
Min/Max Log Configuration/Read-back Select Parameters
CSP File No.
N26
Remote I/O BT
13
CIP Assy. Inst.
29 (Write), 30 (Read)
No. of Elements
9
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Min/Max Log Configuration/Read-back Select
Element
No.
Modbus
Address
Element Name
Range
Default
Value
Comment
0
40901
Password
0…9999
0
Required for configuration, -1 for readback
select, returns -1.
1
40902
Min/max parameter to read
0…73
1
Refer to Interfacing with the Min/Max Log
by Using Communication on page 154
.
2
40903
Read-back mode
0…1
0
3
40904
Enable/disable Min/max log
0…1
1
4
40905
Clear min/max log
0…1
0
5
40906
Timestamp of last min/max clear; year
month/day
hour/minute
second/hsec
1998…2097
-
6
40907
0101…1231
-
7
40908
0000…2359
-
8
40909
0000…5999
-