Setpoint output actions parameters, Setpoint output actions, Refer to setpoint output actions parameters – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 218

218
Publication 1404-UM001F-EN-P - November 2009
Appendix A Powermonitor 3000 Data Tables
Setpoint Output Actions Parameters
Applies to
Refer to Setpoint Setup/Read-back Select and Status Parameters on page 215
PM3000 Type
See table
Setpoint Output Actions
Param.
#
Parameter Name
M4
M5
M
6
M
8
Comment
0
None
•
• •
No output action, but recorded in the event log and Setpoint status
recorded
1
Energize relay and set alarm flag 1
•
• •
Refer to Discrete Data Parameters
2
Energize KYZ and set alarm flag 2
•
• •
3
Set alarm flag 3
•
• •
4
Set alarm flag 4
•
• •
5
Set alarm flag 5
•
• •
6
Set alarm flag 6
•
• •
7
Set alarm flag 7
•
• •
8
Set alarm flag 8
•
• •
9
Set alarm flag 9
•
• •
10
Set alarm flag 10
•
• •
11
Set alarm flag 11
•
• •
12
Set alarm flag 12
•
• •
13
Set alarm flag 13
•
• •
14
Set alarm flag 14
•
• •
15
Set alarm flag 15
•
• •
16
Set alarm flag 16
•
• •
17
Save a trend log record
•
• •
Saves record even if periodic trending is disabled
18
Clear kWh result
•
• •
19
Clear kVARh result
•
• •
20
Clear kVAh result
•
• •
21
Clear Ah result
•
• •
22
Clear all energy results
•
• •