Transient analysis configuration/read-back select, Transient analysis, Configuration/read-back select – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 249: Transient, Analysis configuration/read-back select, Table

Publication 1404-UM001F-EN-P - November 2009
249
Powermonitor 3000 Data Tables Appendix A
Transient Analysis Configuration/Read-back Select Parameters
CSP File No.
F43
Remote I/O BT
44
CIP Assy. Inst.
52 (Write), 53 (Read)
No. of Elements
10
User Configurable No
Data Type
Floating Point
Data Access
Read / Write
PM3000 Type
M8 only
Applies to
Transient analysis metering results
Transient Analysis Configuration/Read-back Select
Element
No.
Modbus
Address
Element Name
Range
Default
Value
Comment
0
-
Password
0…9999
0
Required for configuration, -1 for readback select,
returns -1.
1
-
DeviceNet unique write
identifier
-32,768…32,767
0
Refer to DeviceNet Unique Write Identifier on
page 103
.
2
-
Capture #
0…6
1
Refer to Transient Analysis Configuration on
page 180
.
3
-
Cycle #
1…12
1
4
-
Read-back mode
0…1
0
5
-
Detection mode
0…3
1
6
-
Reserved
0
0
7
-
Auto-threshold set command
0…1
0
8
-
Auto-threshold set duration
1…3600
10
9
-
Auto-threshold set margin
1.0…100.0
20.0
10
-
Voltage trigger threshold
0.1…100.0
10.0
11
-
Current trigger threshold
0.1…100.0
10.0
12
-
Auto-threshold duration time
left
0
0