Metering voltage, current, and frequency result – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 205

Publication 1404-UM001F-EN-P - November 2009
205
Powermonitor 3000 Data Tables Appendix A
Metering Voltage, Current, and Frequency Result Parameters
CSP File No.
F15
Remote I/O BT
38
CIP Assy. Inst.
14
No. of Elements
14
User Configurable No
Data Type
Floating point
Data Access
Read only
PM3000 Type
All
Metering Voltage, Current, and Frequency Result
Element
No.
Modbus
Address
Element name
Units
Range
Comment
0
30101-2
L1 Current
Amps (A)
0.0…999.9x10
21
Refer to Voltage, Current, and Frequency Results on
page 30
1
30103-4
L2 Current
0.0…999.9x10
21
2
30105-6
L3 Current
0.0…999.9x10
21
3
30107-8
Avg. Current
0.0…999.9x10
21
4
30109-10
L1-N Voltage
Volts (V)
0.0…999.9x10
21
5
30111-12
L2-N Voltage
0.0…999.9x10
21
6
30113-14
L3-N Voltage
0.0…999.9x10
21
7
30115-16
Avg. L-N Voltage
0.0…999.9x10
21
8
30117-18
L1-L2 Voltage
0.0 …999.9x10
21
9
30119-20
L2-L3 Voltage
0.0 …999.9x10
21
10
30121-22
L3-L1 Voltage
0.0…999.9x10
21
11
30123-24
Avg L-L Voltage
0.0…999.9x10
21
12
30125-26
Frequency, last cycle
Hertz (Hz) 40.0…75.0
Returns 0 or 999.0 if out of range.
13
30127-28
Metering iteration
-
0…32,767
Increments by 1…32,767, rolls over to 0.