Chapter 7 Data Logging

The

Min/Max Log Results

table is a read-only data table consisting of

11 floating-point elements containing the following information:

Parameter #: See the

Min/Max Log Parameter Listing

table above

Min and max values

Timestamps: for Min and Max values in four-element timestamp
format

Time-of-use

The power monitor provides a Time-of-Use Log. Also called the TOU
log, it provides a one-year time-of-use history of energy usage and
demand. The time-of-use log provides the following:

User-selectable on-peak, mid-peak and off-peak hours

User-selectable off-peak days of the week

Real, reactive and apparent energy usage records

Real, reactive and apparent power demand records

Month-to-date record for the current month

Monthly history for the past year

User-selectable day of month to begin time-of-use logs

The time-of-use log is designed to support simple billing and cost
allocation applications that apply different rates to energy and
demand used at different times.

Time-of-use Hours Selection

Off peak hours are those which occur on off peak days or during
hours not selected as either mid peak or on peak. Hours selected as
both mid peak and on peak will be evaluated as on peak hours.

RSEnergyMetrix software selects the appropriate time-of-use logs to
store energy and demand values based on the time-of-use hours
selection and the off peak day selection.

Time-of-use selection elements are bit mapped parameters. The bits
are mapped as shown in the table below, which depicts the default
values as an example. The default time-of-use periods include the
following:

Mid peak AM8:00…10:59

Mid peak PM3:00…6:59

Peak AM10:00…11:59

Peak PM12:00 noon…2:59