Transient capture clear/read-back data select, Transient, Capture clear/read-back data select – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 251: Transient capture, Clear/read-back data select, Table

Publication 1404-UM001F-EN-P - November 2009
251
Powermonitor 3000 Data Tables Appendix A
Transient Capture Clear/Read-back Data Select Parameters
CSP File No.
N45
Remote I/O BT
17
CIP Assy. Inst.
55 (Write), 56 (Read)
No. of Elements
13
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
M8 only
Applies to
Transient Capture Results Parameters on
Transient Capture Clear/Read-back Data Select
Element
No.
Modbus
Address
Element Name
Range
Default
Value
Comment
0
-
Password
0…9999
0
Required for configuration, -1 for readback select, returns
-1.
1
-
Dnet unique write
identifier
-32,768…32,767
0
Refer to DeviceNet Unique Write Identifier on page 103
.
2
-
Capture number
0…6
1
Refer to Reading Transient Capture Data on page 182
3
-
Channel number
1…7
1
4
-
Block number
See page 90
1
5
-
Read-back mode
0…2
0
6
-
Clear command
0…3
0
7
-
Reserved
0
0
8
-
Reserved
0
0
9
-
Reserved
0
0
10
-
Capture clear status
0…63
-
11
-
Capture ready status
0…63
-
12
-
Reserved
0
0