Appendix A Powermonitor 3000 Data Tables
Event Log Configuration/Read-back Record Select Parameters
CSP File No.
N28
Remote I/O BT
9
CIP Assy. Inst.
32 (Write), 33 (Read)
No. of Elements
6
User Configurable No
Data Type
Integer
Data Access
Read / Write
PM3000 Type
All
Applies to:
Event Log Results Parameters on
Event Log Configuration/Read-back Record Select
Element
No.
Modbus
Address
Element Name
Range
Default
Value
Comment
0
41001
Password
0…9999
0
Required for configuration, -1 for readback
select, returns -1
1
41002
DeviceNet unique write identifier
-32,768…32,767
0
Refer to DeviceNet Unique Write Identifier on
page 103
2
41003
Read-back mode
0…6
2
Refer to Configuring the Event Log by Using
Communication on page 146
3
41004
Enable/disable logging status
input changes
0…1
0
4
41005
# events in the event log
1…50 (M4,M5)
1…100 (M6, M8)
-
5
41006
Enable/disable logging of
time/date set
0…1
1