Harmonic results; odd harmonics 1…21 parameters, Harmonic results; odd harmonics 1…21, Harmonic results; odd harmonics 1…21 parameters on – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 239: Harmonic results

Publication 1404-UM001F-EN-P - November 2009
239
Powermonitor 3000 Data Tables Appendix A
Harmonic Results; Odd Harmonics 1…21 Parameters
CSP File No.
F35
Remote I/O BT
39
CIP Assy. Inst.
42
No. of Elements
14
User Configurable No
Data Type
Floating Point
Data Access
Read only
PM3000 Type
M6, M8 only
Harmonic Results; Odd Harmonics 1…21
Element
No.
Modbus
Address
Element Name
Range
Comment
0
-
Channel # returned
1…7
Refer to Reading Harmonic Analysis Data on page 172
1
-
Type of harmonic data returned
0…1
2
-
1
st
Harmonic (Fundamental)
0.0
3
-
3
rd
Harmonic
0.0…999.9x10
22
4
-
5
th
Harmonic
0.0…999.9x10
22
5
-
7
th
Harmonic
0.0…999.9x10
22
6
-
9
th
Harmonic
0.0…999.9x10
22
7
-
11
th
Harmonic
0.0…999.9x10
22
8
-
13
th
Harmonic
0.0…999.9x10
22
9
-
15
th
Harmonic
0.0…999.9x10
22
10
-
17
th
Harmonic
0.0…999.9x10
22
11
-
19
th
Harmonic
0.0…999.9x10
22
12
-
21
st
Harmonic
0.0…999.9x10
22
13
-
FFT iteration
0…32,767