Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 72

72
Publication 1404-UM001F-EN-P - November 2009
Chapter 4 Communication
TIP
Some legacy power monitor units with optional DeviceNet
communication do no support remotely settable node addressing,
AutoBaud, or Program Baud. You can check whether your power
monitor supports these functions by viewing the Optional
Communication Card status by using your display module.
Communication type 81 does not support these functions, type 88
does. You may also view this status item by a read of assembly
instance 23, element 25.
Optional DeviceNet Communication Configuration Summary
Parameter Description
Range
Default
User
Setting
Node
Address
DeviceNet node
number (MAC ID)
0…64 decimal
63
Baud Rate
DeviceNet
Communication
Rate
0 = 125 Kbps
1 = 250 Kbps
2 = 500 Kbps
3 = Autobaud
4 = Program Baud
0 = 125 Kbps
Bus-off
Interrupt
Specifies response
to a CAN bus-off
interrupt
0 = Hold CAN
chip in reset
1 = Reset CAN
chip and continue
0 = Hold in Reset